Place of Origin: China
Brand Name: Longsun
Model Number: LTZM1E
Minimum Order Quantity: 1 pc
Delivery Time: 15 working days
Payment Terms: L/C, T/T, Western Union, etc.
Residual Current Protection Circuit Breaker
LTZM2L series residual current protection circuit breaker (hereinafter referred to as protector) is a technologically innovative patent product developed by our company in recent years to adapt to the actual environment of safe electricity consumption in urban and rural areas. It is a multi-functional intelligent comprehensive protector integrating the functions of residual current protection, circuit main switch, manual and automatic opening and closing.
LTZM2L series protectors are suitable for low-voltage power grids with three-phase four-wire neutral point directly grounded. In addition to residual current, overload, short circuit and other protections, it also has undervoltage, overvoltage, phase loss, zero loss, etc. with information data display, It is an intelligent product with multiple functions such as information and data query and storage, remote switch and control, switch status signal, prepaid meter control, etc.
This product implements GB14048.2/IEC60947-2 standard.
Normal working conditions
●Ambient temperature: -40℃~40℃;
●Relative air temperature: when the monthly average minimum temperature of the wettest month does not exceed 25°C, the monthly average maximum relative humidity of the month does not exceed 90%, and the condensation on the surface of the product due to temperature changes is taken into account;
●Altitude: no more than 2000 meters;
●Pollution level: level 3;
●Installation category: Ⅲ;
●Installation site: the external magnetic field shall not exceed 5 times of the earth’s magnetic field in any direction;
The main technical parameters
Rated voltage/frequency | AC400V/50Hz three-phase four-wire system (3N) |
Rated current | 100A (65~100 adjustable); 250 (225A) (100~225/250 adjustable); 400A (250~400 adjustable); 630A (400~630 adjustable); 800A (630A-800A adjustable): |
Rated impulse withstand voltage | 8KV |
Rated insulation voltage | AC1KV |
Rated residual operating current | 100, 200, 300, 500, 1000mA |
Rated residual non-operating current | 0.5l△no |
Automatic tracking of residual current | 100~1000mA |
Classification of action characteristics | AC type |
Rated breaking time | 0.3S, 0.5S, delay type |
Delay type limit non-driving time | △t60ms, △t1kms |
Rated undervoltage action value | (105~160V) adjustable |
Stabilized overvoltage action value | (265~300V) adjustable |
Reclosing time | 20s~60s |
Rated short-circuit breaking capacity | See Table 1 for details |
Rated short-time withstand current | See Table 1 for details (Type B) |
Use category | Class A, Class B |
Overcurrent Protection Features | (See Table 2, 3) |
Load Control Protection Features | (See Table 4) |